Variant Number
Vendor-ID: 338 | Device-ID: 2049 | Vendor: Leuze electronic GmbH + Co. KG |
![]() leuze_electronic-logo.png |
IODD Version: V1.0.3 | File Creation Date: 2014-09-10 | Copyright: Leuze electronic GmbH + Co. KG | |
IO-Link Revision: V1.0 | Minimal Cycle Time: 0µs | SIO not supported |
![]() leuze_electronic-ods96-pic.png |
![]() leuze_electronic-ods96-icon.png |
50109294 | ODSL 96B M/L-S12 | Distance sensor |
50109301 | ODKL 96B M/L-S12 | Distance sensor | ||
50127488 | ODSIL 96B M/L-S12 | Distance sensor |
Input Image | ||
Label: | Measured Value | |
Value Range: | 0 ... 25500 | |
Value: | 65534 | Signal error |
Value: | 65535 | Signal too low |
Data Format: | unsigned integer 16 bit |
Index: | 0 | |
Label: | Direct Parameters 1 | |
Description: | ||
Data Format: | record 128 bit, Access via Subindex supported | |
Subindex: | 2 | Bit-Offset = 112 |
Label: | Master Cycle Time | |
Data Format: | unsigned integer 8 bit | |
Subindex: | 3 | Bit-Offset = 104 |
Label: | Min Cycle Time | |
Data Format: | unsigned integer 8 bit | |
Subindex: | 4 | Bit-Offset = 96 |
Label: | Frame Capability | |
Data Format: | unsigned integer 8 bit | |
Subindex: | 5 | Bit-Offset = 88 |
Label: | IO-Link Version ID | |
Data Format: | unsigned integer 8 bit | |
Default Value: | 16 | |
Subindex: | 6 | Bit-Offset = 80 |
Label: | Process Data Input Length | |
Data Format: | unsigned integer 8 bit | |
Subindex: | 7 | Bit-Offset = 72 |
Label: | Process Data Output Length | |
Data Format: | unsigned integer 8 bit | |
Subindex: | 8 | Bit-Offset = 64 |
Label: | Vendor ID 1 | |
Data Format: | unsigned integer 8 bit | |
Subindex: | 9 | Bit-Offset = 56 |
Label: | Vendor ID 2 | |
Data Format: | unsigned integer 8 bit | |
Subindex: | 10 | Bit-Offset = 48 |
Label: | Device ID 1 | |
Data Format: | unsigned integer 8 bit | |
Subindex: | 11 | Bit-Offset = 40 |
Label: | Device ID 2 | |
Data Format: | unsigned integer 8 bit | |
Subindex: | 12 | Bit-Offset = 32 |
Label: | Device ID 3 | |
Data Format: | unsigned integer 8 bit | |
Access Rights: | read only |
Index: | 2 | |
Label: | System Command | |
Description: | ||
Value: | 130 | Restore Factory Setting |
Value: | 176 | Turn Transmitter (laser diode) on |
Value: | 177 | Turn Transmitter (laser diode) off |
Value: | 178 | Pilot Laser toggle |
Data Format: | unsigned integer 8 bit | |
Default Value: | 176 | Turn Transmitter (laser diode) on |
Access Rights: | write only |
Index: | 16 | |
Label: | Vendor Name | |
Description: | ||
Data Format: | string 40 Byte | |
Default Value: | Leuze electronic GmbH + Co. KG | |
Access Rights: | read only |
Index: | 17 | |
Label: | Vendor Text | |
Description: | ||
Data Format: | string 64 Byte | |
Default Value: | Leuze electronic - the sensor people | |
Access Rights: | read only |
Index: | 18 | |
Label: | Product Name | |
Description: | ||
Data Format: | string 64 Byte | |
Access Rights: | read only |
Index: | 19 | |
Label: | Product ID | |
Description: | ||
Data Format: | string 64 Byte | |
Access Rights: | read only |
Index: | 20 | |
Label: | Product Text | |
Description: | ||
Data Format: | string 64 Byte | |
Default Value: | distance sensor | |
Access Rights: | read only |
Index: | 21 | |
Label: | Serial Number | |
Description: | ||
Data Format: | string 16 Byte | |
Access Rights: | read only |
Index: | 22 | |
Label: | Hardware Version | |
Description: | ||
Data Format: | string 64 Byte | |
Access Rights: | read only |
Index: | 23 | |
Label: | Firmware Version | |
Description: | ||
Data Format: | string 64 Byte | |
Access Rights: | read only |
Index: | 40 | |
Label: | Process Data Input | |
Description: | ||
Data Format: | processDataIn 16 bit | |
Access Rights: | read only |
Index: | 190 | |
Label: | Sensor Status | |
Description: | Sensor Status | |
Data Format: | record 8 bit, Access via Subindex not supported | |
Subindex: | 1 | Bit-Offset = 0 |
Label: | Receiver Signal Quality | |
Value: | 0 | good |
Value: | 2 | too low |
Value: | 4 | weak |
Value: | 6 | too low |
Data Format: | unsigned integer 3 bit | |
Subindex: | 2 | Bit-Offset = 3 |
Label: | Transmitter (laser diode) | |
Value: | false | active |
Value: | true | inactive |
Data Format: | boolean | |
Subindex: | 3 | Bit-Offset = 4 |
Label: | Measured Values | |
Value: | false | outside of the calibrated range |
Value: | true | inside of the calibrated range |
Data Format: | boolean | |
Default Value: | true | inside of the calibrated range |
Access Rights: | read only |
Index: | 192 | |
Label: | Variant Number | |
Description: | variant number of IO-Link distance sensor device | |
Value: | 0 | ODSL Variant |
Value: | 1 | ODKL Variant |
Value: | 6 | ODSIL Variant |
Data Format: | unsigned integer 8 bit | |
Default Value: | 0 | ODSL Variant |
Access Rights: | read only |
Index: | 193 | |
Label: | Resolution | |
Description: | Distance = Measured Value * Resolution | |
Value: | 0 | 1 mm |
Value: | 1 | 0.1 mm |
Value: | 2 | 0.01 mm |
Data Format: | unsigned integer 8 bit | |
Default Value: | 0 | 1 mm |
Access Rights: | read only |
Index: | 200 | |
Label: | Measurement Mode | |
Description: | Measurement Mode defines the preferred detection behavior of the sensor. | |
Value: | 0 | Standard |
Value: | 1 | Precision |
Value: | 2 | Speed |
Data Format: | unsigned integer 16 bit | |
Default Value: | 1 | Precision |
Access Rights: | read and write |
Index: | 201 | |
Label: | Filter Type | |
Description: | Averaging: Floating average calculation over n measurements; Center Filter: Average calculation with spike suppression | |
Value: | 0 | Off (no filtering) |
Value: | 1 | Averaging |
Value: | 2 | Center Filter |
Data Format: | unsigned integer 16 bit | |
Default Value: | 0 | Off (no filtering) |
Access Rights: | read and write |
Index: | 202 | |
Label: | Measurement Count (Filter Type = Averaging) | |
Description: | The floating average is calculated over 1 to 99 measured values. Output data is refreshed after each calculation. When the measured value changes stepwise, the output data will in-/decrease linearly to the new value. | |
Value Range: | 1 ... 99 | |
Data Format: | unsigned integer 16 bit | |
Default Value: | 30 | |
Access Rights: | read and write |
Index: | 203 | |
Label: | Measurement Count (Filter Type = Center Filter) | |
Description: | The average calculation includes 10 to 50 single measured values. Spikes are suppressed. | |
Value: | 0 | 10 |
Value: | 1 | 20 |
Value: | 2 | 30 |
Value: | 3 | 40 |
Value: | 4 | 50 |
Data Format: | unsigned integer 16 bit | |
Default Value: | 0 | 10 |
Access Rights: | read and write |
Index: | 204 | |
Label: | Filter depth (Filter Type = Center Filter) | |
Description: | Filter depth defines the bandwidth of the spike suppression. | |
Value: | 0 | Coarse |
Value: | 1 | Medium |
Value: | 2 | Fine |
Data Format: | unsigned integer 16 bit | |
Default Value: | 0 | Coarse |
Access Rights: | read and write |
Index: | 205 | |
Label: | Sensor Display | |
Description: | Auto: Maximum intensity when button is pressed; dimmed to lower intensity while stand-by (after 1 minute). | |
Value: | 0 | On |
Value: | 1 | Off |
Value: | 2 | Auto |
Data Format: | unsigned integer 16 bit | |
Default Value: | 2 | Auto |
Access Rights: | read and write |
Index: | 206 | |
Label: | Key Lock | |
Description: | If activated, local control at the sensor device is disabled. | |
Value: | 0 | not activated |
Value: | 1 | activated |
Data Format: | unsigned integer 16 bit | |
Default Value: | 0 | not activated |
Access Rights: | read and write |
Index: | Label: | Access Rights: |
---|---|---|
16 | Vendor Name | read only |
17 | Vendor Text | read only |
18 | Product Name | read only |
19 | Product ID | read only |
20 | Product Text | read only |
21 | Serial Number | read only |
22 | Hardware Version | read only |
23 | Firmware Version | read only |
40 | Process Data Input | read only |
193 | Resolution | read only |
Index: | Label: | Access Rights: |
---|---|---|
2 | System Command | write only |
16 | Vendor Name | read only |
17 | Vendor Text | read only |
18 | Product Name | read only |
19 | Product ID | read only |
20 | Product Text | read only |
21 | Serial Number | read only |
22 | Hardware Version | read only |
23 | Firmware Version | read only |
40 | Process Data Input | read only |
193 | Resolution | read only |
200 | Measurement Mode | read only |
201 | Filter Type | read only |
202 | Measurement Count (Filter Type = Averaging) | read only |
203 | Measurement Count (Filter Type = Center Filter) | read only |
204 | Filter depth (Filter Type = Center Filter) | read only |
205 | Sensor Display | read and write |
206 | Key Lock | read only |
Index: | Label: | Access Rights: |
---|---|---|
2 | System Command | write only |
16 | Vendor Name | read only |
17 | Vendor Text | read only |
18 | Product Name | read only |
19 | Product ID | read only |
20 | Product Text | read only |
21 | Serial Number | read only |
22 | Hardware Version | read only |
23 | Firmware Version | read only |
40 | Process Data Input | read only |
190 | Sensor Status | read only |
193 | Resolution | read only |
200 | Measurement Mode | read and write |
201 | Filter Type | read and write |
202 | Measurement Count (Filter Type = Averaging) | read and write |
203 | Measurement Count (Filter Type = Center Filter) | read and write |
204 | Filter depth (Filter Type = Center Filter) | read and write |
205 | Sensor Display | read and write |
206 | Key Lock | read and write |