Version: V1.1Release Date: 2016-07-22


PRK3C.A3/LP
Vendor ID 338 (0x0152) Vendor Logo
Vendor Name Leuze electronic GmbH + Co. KG
Vendor Text Leuze electronic the sensor people
Vendor URL http://www.leuze.com
Device ID 2118 (0x000846)
DeviceFamily BR 3C
Features
Block Parameter no
Data Storage no
Communication
IO-Link Revision V1.1
Transmission Rate38400 bit/s (COM2)
Minimum Cycle Time 2.3 ms
SIO Mode Supported yes
M-Sequence CapabilityPREOPERATE = TYPE_0 with 1 octet on-request data
OPERATE = TYPE_2_5 with 1 octet on-request data
ISDU not supported
Device Variant PRK3C IO-Link
Description PRK3C IO-Link 2.5 without ISDU
Product ID PRK3C.A3/LP
Device Icon Device Icon
Device Symbol Device Symbol
Connection TypeM12-5 connector
- pin 1 brown; L+
- pin 2 white; Other
- pin 3 (light) blue; L-
- pin 4 black; C/Q
- pin 5 grey (slate); NC

ProcessData id=PD_ProcessData (condition V_DirectParameters.26 == 0)

ProcessDataIn "Sensor Switching Signals (PDI)" id=PD_ProcessDataIn

bit length: 8
data type: 8-bit Record

subindex bit offset data type allowed values default value acc. restr. mod. other var. excl. from DS name description
1 0 Boolean Q
2 1 Boolean Warnung
3 2 Boolean Status
Octet 0
bit offset 7 6 5 4 3 2 1 0
subindex / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / 3 2 1

ProcessDataOut "PDO_function" id=PD_ProcessDataOut

bit length: 1
data type: Boolean
Octet 0
bit offset 7 6 5 4 3 2 1 0
element bit sign ext.  

ProcessData id=PD_ProcessDataAdc (condition V_DirectParameters.26 == 1)

ProcessDataIn "Sensor Switching Signals (PDI)" id=PD_ProcessDataInAdc

bit length: 8
data type: 8-bit Record

subindex bit offset data type allowed values default value acc. restr. mod. other var. excl. from DS name description
1 0 Boolean Q
2 1 7-bit UInteger Empfangssignal
Octet 0
bit offset 7 6 5 4 3 2 1 0
subindex 2 1
element bit 6 5 4 3 2 1 0  

ProcessDataOut "PDO_function" id=PD_ProcessDataOutAdc

bit length: 1
data type: Boolean
Octet 0
bit offset 7 6 5 4 3 2 1 0
element bit sign ext.  

Standard Variable "Direkte Parameter 1" index=0 id=V_DirectParameters_1

data type: 128-bit Record
access rights: rw
excluded from data storage

subindex bit offset data type allowed values default value acc. restr. mod. other var. excl. from DS name description
1 120 8-bit UInteger ro Reserviert
2 112 8-bit UInteger 0 ro Master Zykluszeit
3 104 8-bit UInteger 23 ro Minimale Zykluszeit
4 96 8-bit UInteger 0 ro Telegramm-Fähigkeit
5 88 8-bit UInteger 17 ro IO-Link Versions-ID
6 80 8-bit UInteger 72 ro Prozessdatenlänge Eingang
7 72 8-bit UInteger 1 ro Prozessdatenlänge Ausgang
8 64 8-bit UInteger 1 ro Hersteller-ID 1
9 56 8-bit UInteger 82 ro Hersteller-ID 2
10 48 8-bit UInteger 0 ro Geräte-ID 1
11 40 8-bit UInteger 16 ro Geräte-ID 2
12 32 8-bit UInteger 2 ro Geräte-ID 3
13 24 8-bit UInteger ro Reserviert
14 16 8-bit UInteger ro Reserviert
15 8 8-bit UInteger ro Reserviert
16 0 8-bit UInteger 160 = Quittierung bei Fehler oder 2-Punkt-Teach, 161 = Standard, 162 = Sensitive Teach (leere Flasche), 170 = Auf Konfigurationsbetrieb umschalten, 171 = Letzter Teachzustand (WORKING) laden, 172 = Werkseitige Einstellungen wiederherstellen, 173 = Aktuelle Parameter dauerhaft speichern, 174 = Sensorbetrieb einschalten, 191 = Prozessdatendarstellung auf Analogwert umschalten wo X Standardkommando

octet 0 1 2 3 4 5 6 7
bit offset 127 - 120 119 - 112 111 - 104 103 - 96 95 - 88 87 - 80 79 - 72 71 - 64
subindex 1 2 3 4 5 6 7 8
element bit 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0

octet 8 9 10 11 12 13 14 15
bit offset 63 - 56 55 - 48 47 - 40 39 - 32 31 - 24 23 - 16 15 - 8 7 - 0
subindex 9 10 11 12 13 14 15 16
element bit 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0

Standard Variable "Direkte Parameter 2" index=1 id=V_DirectParameters_2

data type: 128-bit Record
access rights: rw
excluded from data storage

subindex bit offset data type allowed values default value acc. restr. mod. other var. excl. from DS name description
1 120 8-bit UInteger Gerätespezifischer Parameter 1
2 112 8-bit UInteger Gerätespezifischer Parameter 2
3 104 8-bit UInteger Gerätespezifischer Parameter 3
4 96 8-bit UInteger Gerätespezifischer Parameter 4
5 88 8-bit UInteger Gerätespezifischer Parameter 5
6 80 8-bit UInteger Gerätespezifischer Parameter 6
7 72 8-bit UInteger Gerätespezifischer Parameter 7
8 64 8-bit UInteger Gerätespezifischer Parameter 8
9 56 8-bit UInteger Gerätespezifischer Parameter 9
10 48 8-bit UInteger Gerätespezifischer Parameter 10
11 40 8-bit UInteger Gerätespezifischer Parameter 11
12 32 8-bit UInteger Gerätespezifischer Parameter 12
13 24 8-bit UInteger Gerätespezifischer Parameter 13
14 16 8-bit UInteger Gerätespezifischer Parameter 14
15 8 8-bit UInteger Gerätespezifischer Parameter 15
16 0 8-bit UInteger Gerätespezifischer Parameter 16

octet 0 1 2 3 4 5 6 7
bit offset 127 - 120 119 - 112 111 - 104 103 - 96 95 - 88 87 - 80 79 - 72 71 - 64
subindex 1 2 3 4 5 6 7 8
element bit 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0

octet 8 9 10 11 12 13 14 15
bit offset 63 - 56 55 - 48 47 - 40 39 - 32 31 - 24 23 - 16 15 - 8 7 - 0
subindex 9 10 11 12 13 14 15 16
element bit 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0 7 - 0

DirectParameterOverlay "DP" id=V_DirectParameters

data type: 128-bit Record
access rights: rw
excluded from data storage

subindex bit offset data type allowed values default value acc. restr. mod. other var. excl. from DS name description
2 104 8-bit UInteger Ausschaltschwelle Ausschaltschwelle in LSB Um Hysterese größer als Einschaltschwelle Wird bei Teachsensoren beim Teach berechnet. Wird bei Sensoren ohne Teach vom Entwickler festgelegt
3 96 8-bit UInteger Einschaltschwelle Einschaltschwelle in LSB: Wird bei Teachsensoren beim Teach berechnet. Wird bei Sensoren ohne Teach vom Entwickler festgelegt
6 77 Boolean false = Aus, true = Ein 1 Tastensperre Taste am Gerät sperren; IO-Link Parameter hat Priorität gegenüber Leitung/PD
8 74 2-bit UInteger 0 = inv. Schaltausgang, 1 = Schaltausgang 0 Logische Funktion von Q2
10 70 2-bit UInteger 0 = Einschaltverzögerung, 1 = Ausschaltverzögerung, 2 = Impulsverlängerung, 3 = Impulsunterdrückung 1 Funktionsauswahl der Zeitstufe Auswahl der Art der Zeitfunktion:
11 68 2-bit UInteger 0 = 1ms, 1 = 10ms, 2 = 100ms, 3 = 1000ms 1 Zeitbasis der Zeitstufe 1ms, 10ms, 100ms, 1000ms
12 64 4-bit UInteger 1 Faktor für Zeitbasis der Zeitstufe Vielleicht auch 1 Byte, wenn möglich, dann mit anderer Basis)
18 58 Boolean false = hellschaltend, true = dunkelschaltend 0 H/D-Umschaltung Hell-/Dunkel-Umschaltung; invertiert Logik auf allen Schaltausgängen; wirkt nach einer optionalen Zeitstufe (im Gegensatz zu bisherigen Leuze-Lösungen wie BR96)
20 56 Boolean false = Aus, true = Ein 0 Zeitstufe (wirkt auf Objekt) Interne Zeitstufe einschalten
25 16 8-bit UInteger Teachwert2 Wird bei Teachsensoren beim Teach ermittelt. Teachwert 2 wird nur für ST2P benötigt. Teachwert2 = Signalhub, ermittelt beim Teach auf Reflektor oder Objekt in LSB (AP - ADC-Wert)
26 8 8-bit UInteger 0 = Schaltsignale, 1 = Anlogsignal und Schaltausgang 0 ro Bedeutung der Prozess-Eingangsdaten Die Variable kennzeichnet den Inhalt der PDI
32 127 Boolean false = abgeschlossen, true = in Bearbeitung 0 ro Status Teachfunktion / Kommando Wird bei jedem Kommando aktualisiert. Die weiteren Statusbit sind gültig, wenn Funktion abgeschlossen
33 126 Boolean false = nein, true = ja 0 ro Kommando akzeptiert
36 123 Boolean false = nein, true = ja 0 ro Teachfehler
37 122 Boolean false = nein, true = ja 0 ro Alte Werte wiederhergestellt
38 121 Boolean false = nein, true = ja 0 ro Empfangspegel zu groß
39 120 Boolean false = nein, true = ja 0 ro Empfangspegel zu gering
Octet 0 (= subindex 1)
bit offset 127 126 125 124 123 122 121 120
"subindex" 32 33 / / / / / / / / / / / / 36 37 38 39
Octet 1 (= subindex 2)
bit offset 119 118 117 116 115 114 113 112
"subindex" / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
Octet 2 (= subindex 3)
bit offset 111 110 109 108 107 106 105 104
"subindex" 2
element bit 7 6 5 4 3 2 1 0
Octet 3 (= subindex 4)
bit offset 103 102 101 100 99 98 97 96
"subindex" 3
element bit 7 6 5 4 3 2 1 0
Octet 4 (= subindex 5)
bit offset 95 94 93 92 91 90 89 88
"subindex" / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
Octet 5 (= subindex 6)
bit offset 87 86 85 84 83 82 81 80
"subindex" / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
Octet 6 (= subindex 7)
bit offset 79 78 77 76 75 74 73 72
"subindex" / / / / / / / / / / / / 6 / / / / / / 8 / / / / / / / / / / / /
element bit         1 0    
Octet 7 (= subindex 8)
bit offset 71 70 69 68 67 66 65 64
"subindex" 10 11 12
element bit 1 0 1 0 3 2 1 0
Octet 8 (= subindex 9)
bit offset 63 62 61 60 59 58 57 56
"subindex" / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / 18 / / / / / / 20
Octet 9 (= subindex 10)
bit offset 55 54 53 52 51 50 49 48
"subindex" / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
Octet 10 (= subindex 11)
bit offset 47 46 45 44 43 42 41 40
"subindex" / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
Octet 11 (= subindex 12)
bit offset 39 38 37 36 35 34 33 32
"subindex" / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
Octet 12 (= subindex 13)
bit offset 31 30 29 28 27 26 25 24
"subindex" / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /
Octet 13 (= subindex 14)
bit offset 23 22 21 20 19 18 17 16
"subindex" 25
element bit 7 6 5 4 3 2 1 0
Octet 14 (= subindex 15)
bit offset 15 14 13 12 11 10 9 8
"subindex" 26
element bit 7 6 5 4 3 2 1 0
Octet 15 (= subindex 16)
bit offset 7 6 5 4 3 2 1 0
"subindex" / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /

Observer Menus

Identification Menu
V_DirectParameters_1.Hersteller-ID 1
V_DirectParameters_1.Hersteller-ID 2
V_DirectParameters_1.Geräte-ID 1
V_DirectParameters_1.Geräte-ID 2
V_DirectParameters_1.Geräte-ID 3
V_DirectParameters.Bedeutung der Prozess-Eingangsdaten

Parameter Menu
Kommandos
V_DirectParameters_1.Standardkommando, wo Button:=161
V_DirectParameters_1.Standardkommando, wo Button:=162
V_DirectParameters_1.Standardkommando, wo Button:=170
V_DirectParameters_1.Standardkommando, wo Button:=171
V_DirectParameters_1.Standardkommando, wo Button:=172
V_DirectParameters_1.Standardkommando, wo Button:=173
V_DirectParameters_1.Standardkommando, wo Button:=174
Description=Sensorbetrieb einschalten
V_DirectParameters_1.Standardkommando, wo Button:=191
Funktionsstatus
V_DirectParameters.Status Teachfunktion / Kommando
V_DirectParameters.Kommando akzeptiert
V_DirectParameters.Teachfehler
V_DirectParameters.Alte Werte wiederhergestellt
V_DirectParameters.Empfangspegel zu groß
V_DirectParameters.Empfangspegel zu gering
V_DirectParameters.Bedeutung der Prozess-Eingangsdaten
Schaltschwellen
V_DirectParameters.Teachwert2
Steuerregister0 für die logische Funktion von In2 und Out2
V_DirectParameters.Tastensperre
V_DirectParameters.Logische Funktion von Q2
Parameter Steuerregister
V_DirectParameters.H/D-Umschaltung
V_DirectParameters.Zeitstufe (wirkt auf Objekt)
Zeitstufe
V_DirectParameters.Funktionsauswahl der Zeitstufe
V_DirectParameters.Zeitbasis der Zeitstufe
V_DirectParameters.Faktor für Zeitbasis der Zeitstufe

Diagnosis Menu
V_DirectParameters_1.Master Zykluszeit
V_DirectParameters_1.Minimale Zykluszeit
V_DirectParameters_1.Telegramm-Fähigkeit
V_DirectParameters_1.IO-Link Versions-ID
V_DirectParameters_1.Prozessdatenlänge Eingang
V_DirectParameters_1.Prozessdatenlänge Ausgang

Maintenance Menus

Identification Menu
V_DirectParameters_1.Hersteller-ID 1
V_DirectParameters_1.Hersteller-ID 2
V_DirectParameters_1.Geräte-ID 1
V_DirectParameters_1.Geräte-ID 2
V_DirectParameters_1.Geräte-ID 3
V_DirectParameters.Bedeutung der Prozess-Eingangsdaten

Parameter Menu
Kommandos
V_DirectParameters_1.Standardkommando, wo Button:=161
V_DirectParameters_1.Standardkommando, wo Button:=162
V_DirectParameters_1.Standardkommando, wo Button:=170
V_DirectParameters_1.Standardkommando, wo Button:=171
V_DirectParameters_1.Standardkommando, wo Button:=172
V_DirectParameters_1.Standardkommando, wo Button:=173
V_DirectParameters_1.Standardkommando, wo Button:=174
Description=Sensorbetrieb einschalten
V_DirectParameters_1.Standardkommando, wo Button:=191
Funktionsstatus
V_DirectParameters.Status Teachfunktion / Kommando
V_DirectParameters.Kommando akzeptiert
V_DirectParameters.Teachfehler
V_DirectParameters.Alte Werte wiederhergestellt
V_DirectParameters.Empfangspegel zu groß
V_DirectParameters.Empfangspegel zu gering
V_DirectParameters.Bedeutung der Prozess-Eingangsdaten
Schaltschwellen
V_DirectParameters.Teachwert2
Steuerregister0 für die logische Funktion von In2 und Out2
V_DirectParameters.Tastensperre
V_DirectParameters.Logische Funktion von Q2
Parameter Steuerregister
V_DirectParameters.H/D-Umschaltung
V_DirectParameters.Zeitstufe (wirkt auf Objekt)
Zeitstufe
V_DirectParameters.Funktionsauswahl der Zeitstufe
V_DirectParameters.Zeitbasis der Zeitstufe
V_DirectParameters.Faktor für Zeitbasis der Zeitstufe

Diagnosis Menu
V_DirectParameters_1.Master Zykluszeit
V_DirectParameters_1.Minimale Zykluszeit
V_DirectParameters_1.Telegramm-Fähigkeit
V_DirectParameters_1.IO-Link Versions-ID
V_DirectParameters_1.Prozessdatenlänge Eingang
V_DirectParameters_1.Prozessdatenlänge Ausgang

Specialist Menus

Identification Menu
V_DirectParameters_1.Hersteller-ID 1
V_DirectParameters_1.Hersteller-ID 2
V_DirectParameters_1.Geräte-ID 1
V_DirectParameters_1.Geräte-ID 2
V_DirectParameters_1.Geräte-ID 3
V_DirectParameters.Bedeutung der Prozess-Eingangsdaten

Parameter Menu
Kommandos
V_DirectParameters_1.Standardkommando, wo Button:=161
V_DirectParameters_1.Standardkommando, wo Button:=162
V_DirectParameters_1.Standardkommando, wo Button:=170
V_DirectParameters_1.Standardkommando, wo Button:=171
V_DirectParameters_1.Standardkommando, wo Button:=172
V_DirectParameters_1.Standardkommando, wo Button:=173
V_DirectParameters_1.Standardkommando, wo Button:=174
Description=Sensorbetrieb einschalten
V_DirectParameters_1.Standardkommando, wo Button:=191
Funktionsstatus
V_DirectParameters.Status Teachfunktion / Kommando
V_DirectParameters.Kommando akzeptiert
V_DirectParameters.Teachfehler
V_DirectParameters.Alte Werte wiederhergestellt
V_DirectParameters.Empfangspegel zu groß
V_DirectParameters.Empfangspegel zu gering
V_DirectParameters.Bedeutung der Prozess-Eingangsdaten
Schaltschwellen
V_DirectParameters.Teachwert2
Steuerregister0 für die logische Funktion von In2 und Out2
V_DirectParameters.Tastensperre
V_DirectParameters.Logische Funktion von Q2
Parameter Steuerregister
V_DirectParameters.H/D-Umschaltung
V_DirectParameters.Zeitstufe (wirkt auf Objekt)
Zeitstufe
V_DirectParameters.Funktionsauswahl der Zeitstufe
V_DirectParameters.Zeitbasis der Zeitstufe
V_DirectParameters.Faktor für Zeitbasis der Zeitstufe

Diagnosis Menu
V_DirectParameters_1.Master Zykluszeit
V_DirectParameters_1.Minimale Zykluszeit
V_DirectParameters_1.Telegramm-Fähigkeit
V_DirectParameters_1.IO-Link Versions-ID
V_DirectParameters_1.Prozessdatenlänge Eingang
V_DirectParameters_1.Prozessdatenlänge Ausgang

Note: This page shows the content of an IODD file transformed into HTML format. In the case of disparity between this and the XML view, the content of the XML file takes precedence.
Created by IODD Viewer V1.1.